Mho Relay | Admittance or angular admittance relays
Luciano Bertene
Structure and working principle of Mho relay
A simple form of Mhorelay Admittanceor angular admittance relays as shown in the following figure:
It is a kind of cup with electromagnetic induction MHO relay .
The torque equation is T = K 1 VI (Φ – α) – K 2 v 2 –K 3
The upper and lower poles are excited by a voltage V to produce a polarizing flux. The capacitor connected in series provides a storage function. The left pole is excited by a current, which is the operational quantity. The left pole interacts with the due to current I polarized flow due to V produces the Operating torque K 1 VI Cos (Φ – α)
The angle α can be adjusted by adjusting the resistance in Phase shift circuit provided on the left pole. The right pole is excited by the voltage and the flux it produces interacts with the polarizing flux to produce the Holding Torque K 2 v 2 .
The mho Relay measures a component of Allow S ∠θ. But its characteristics when you look at it on the Impedance Diagram (i.e. RX Chart ) is a circle that passes through the origin shown in the figure. It is a directional relay in nature as it detects the fault only in the forward direction. The relay is called Mho relay because its characteristic is a straight line when in Intake diagram (GB axes i.e. conductance-susceptance axes) as in the figure.
Read: Directional Overcurrent Relay
Read: Solid State Relay or Static Relay
Characteristic expression of the Mho relay
The operating torque for an Mho relay occurs through the VI element and the restraining torque occurs through the voltage element.
Therefore mho relay can as voltage dependent directional relay .
T = K 1 VI Cos (Φ – α) –K 2 v 2 where the effect of the spring is neglected.
K 2 v 2 < K 1 VI Cos (Φ – α)
K2V 1I cos (Φ – α)
(V/I cos (Φ – α)) < K 1 /K 2 or (V/I) < (K 1 /K 2 ) Cos (Φ – α) or Z < (K 1 /K 2 )Cos (Φ – α)
Under equilibrium conditions, the operating torque is equal to the holding torque.
that is, K 1 VICos (Φ – α) = K 2 v 2
(I/V)Cos (Φ – α) = (K 2 K 1 ) =K
(1/Z) = (K / Cos (Φ – α)) = Y
Y = K / Cos (Φ – α) = admittance in mho.
These MHO relay units are used to protect a section of line. Unit I is a high speed unit designed to protect 80% to 90% of the line section. Unit II protects the remainder of the line section and its range extends up to 50% of the adjacent line section. Unit III is intended for backup protection of the adjacent line section. Units II and III operate with a predefined time delay, typically 0.2s to 0.5s and 0.4s to 1s, respectively. The time delay characteristic is gradual, as shown in the figure.
Operation of impedance and Mho relays during power swing
Comparison of Mho characteristic and impedance characteristic under voltage fluctuations AB is the line to be protected. The relay with impedance characteristic trips even at fault points behind position A, which is nothing more than a “fault trip”.
On the other hand, the relay with Mho characteristic, which requires a comparatively small circular area for line AB, does not detect the errors behind A. Therefore, many points covered by the impedance characteristic are in the negative torque range of the Mho characteristic.
The location of power fluctuation that occurs in long transmission lines during false synchronization, etc. is a transient phenomenon and a curve that enters the operating range of an impedance relay before the Mho relay. This is undesirable because the transmission line itself will be turned off by the impedance relay protection before the power fluctuation can subside. However, with the strong and rapid occurrence of a power fluctuation, the location may enter the operating range of the Mho relay, which intervenes and disconnects the line, which is also undesirable. Therefore, to avoid this kind of situation, mho offset relay is used as shown below.
During power swing, the location of the impedance measured by the relay moves along the curve. As soon as it enters the positive torque range of the Mho offset characteristic (point P), the Mho offset relay is activated and blocks the BC line measuring relay. Therefore, Mho relay does not operate during power swing.
O aço patinável, também conhecido como aço corten, tem se destacado como uma alternativa eficiente e econômica para a proteção anticorrosiva de estruturas metálicas. Essa tecnologia inovadora permi...
Os carros são chamados de "máquinas que mudam o mundo". Como a indústria automobilística tem uma forte correlação industrial, ela é considerada um símbolo importante do nível de desenvolvimento eco...
A soldagem por arco submerso (SAW) é uma técnica amplamente utilizada na indústria, conhecida por sua alta taxa de deposição e capacidade de soldar chapas grossas e estruturas pesadas. Este process...
A escassez de água é um desafio global cada vez mais urgente. Com a crescente demanda por recursos hídricos e os impactos das mudanças climáticas, é essencial que adotemos soluções sustentáveis par...
Cálculo de Deformação Elástica Limite em Barras de Aço
A análise da deformação elástica limitada é um importante aspecto do desenho e construção de estruturas metálicas, pois permite identificar o...
Mesmo com a sobretaxa de 25% imposta pelos EUA, as exportações brasileiras de aço e automóveis para o mercado norte-americano cresceram até 20,5% no primeiro trimestre de 2025, mostrando a resiliên...
O cenário econômico brasileiro tem sido alvo de constante atenção e análise por parte dos especialistas do mercado financeiro. Recentemente, o Boletim Focus do Banco Central do Brasil elevou a prev...
O Índice de Confiança da Indústria (ICI) do FGV IBRE permaneceu estável em março, com uma leve variação de 0,1 ponto, alcançando 98,4. Essa estabilidade sugere que as expectativas dos empresários e...