What should be connected to an emergency generator in a commercial building?

Commercial buildings are characterized by the continuous presence of a large number of occupants, which means that security must be among the top priorities of the owner companies. When addressing the topic of backup generators, the New York Building Code classifies loads into two main categories: emergency loads and standby loads.

Emergency loads include building equipment and systems that would create life-threatening conditions if they stopped operating. For example, exit signs and stair lighting are always considered emergency loads, as it is very difficult to evacuate a building without them.

Standby loads may cause disruption or discomfort if they stop operating, but do not create risks such as those involved if an emergency load loses power. Keep in mind, however, that backup power for some backup loads is mandatory, especially loads that simplify troubleshooting during an electrical service outage or if they are useful for rescue operations during an emergency.

General Emergency and Backup Power Requirements for Commercial Occupancies in New York

Commercial buildings in New York City typically fall into one of the following occupancy classifications:

  • Assembly groups A-1 to A-5, which include restaurants.
  • Business Group B, which includes office buildings
  • Educational Group E, which includes schools.
  • Institutional Groups I-1 to I-4, which include hospitals.
  • Grupo Mercantil M, which includes retail.

The New York Building Code provides a general list of emergency and standby loads for which standby power is mandatory, but there are additional requirements for the following occupancy groups:

  • Assembly group A, all subgroups
  • Business Group B and Educational Group E, where the building occupied space less than 75 feet above the lowest fire vehicle access and a gross area in excess of 15,000 ft2 per floor or at least 100,000 ft2 in total.
  • Institutional Group I-3: Correctional centers and psychiatric hospitals
  • Special requirements also apply to indoor shopping malls, high-rise buildings and underground locations.

The following table provides a list of all loads that must be connected to emergency power and standby power in commercial occupancies in New York. Specific requirements for some occupancies or building types are provided in the next section.

EMERGENCY POWER

LEGALLY REQUIRED STANDBY POWER

1) Exit signals
2) Means of exit lighting
3) Elevator controls, cabin lights and ventilation

1) Smoke control systems
2) Horizontal sliding doors
3) Membrane structures
4) Elevators
5) Smoke-proof cabinets
6) Pressurized elevator shafts

Emergency and Standby Power: Special Cases

The New York Building Code establishes additional requirements for some occupancy groups or building types. They are summarized in the following table, and remember that the general requirements still apply.

OCCUPATION OR
CONSTRUCTION TYPE

Emergency power

Mandatory standby power

A group

1) Voice communication and alarm systems.

None beyond general requirements.

Groups B and E that have access for fire engines and space conditions

1) Emergency voice and alarm communication systems. This includes auxiliary radiocommunication systems (ARCs) used by the Fire Department, even if they were installed voluntarily.

2) Automatic fire detection systems.

3) Fire alarms.

4) Electric fire pumps (manual, automatic, sprinkler booster pumps).

1) Stair pressurization systems.

2) At least three elevators with manual transfer to other elevators as needed.

3) Fire command center power and lighting.

Group I-3

1) Electric doors and locks.

None beyond general requirements.

Indoor shopping mall above 50,000 feet 2

None beyond general requirements.

1) Voice communication and emergency alarm system.

Skyscrapers (non-residential)

1) Emergency voice and alarm communication systems. This includes auxiliary radio communication systems (ARCs) used by the Fire Department.

2) Automatic fire detection systems.

3) Fire alarms.

4) Electric fire pumps (manual, automatic, sprinkler booster pumps, etc.).

1) Fire command center power and lighting.

2) Stair pressurization systems.

Underground

1) Emergency voice and alarm communication systems. This includes auxiliary radio communication systems (ARCs) used by the Fire Department.

2) Automatic fire detection systems.

3) Fire alarms.

1) Electric fire pumps.

2) Stair pressurization systems.

Optional standby power: additional requirements

All loads not included in the tables above are considered optional standby loads, meaning that the New York Building Code does not require a standby power system for them, but they may be installed anyway if deemed appropriate. It is important to note, however, that the following loads must be added to any optional standby loads when sizing the generator:

  • Fire alarm systems
  • Emergency light
  • At least one elevator serving all floors, in buildings with occupied floors more than 75 feet above the lowest fire truck access

Although these loads are typically covered by emergency or mandatory standby power systems, the code requires that they be counted toward any optional standby system as a fail-safe measure. Additionally, the code allows fuel supply to be shared between optional emergency and standby generators. Additional equipment required for generator operation can also be shared between emergency units and optional standby units.

When is optional standby power recommended?

There are many loads in commercial buildings that are not legally required to have backup power. When determining what to connect to an optional backup power system, the best recommendation is to work closely with the property owner and use common sense.

Cooling systems

When refrigeration systems stop working, it is only a matter of time before the products and supplies they contain begin to degrade. This may not be a critical problem in an office building that has just a few small refrigerators, but it can have serious consequences in a restaurant or hospital where large quantities of food or medical supplies require low-temperature storage.

In these cases, even if a backup power system is not legally required, it is in the company's best interest to install it. In both cases, the omission of the backup power system can have consequences for human health. Furthermore, even if spoiled food or medical supplies are discarded, it represents a financial loss for the company.

Water pumping systems

Water supply is a fundamental building system, especially when there are kitchens and bathrooms. Therefore, optional backup power is recommended if the building relies on a water booster pump; otherwise, an interruption in electrical service will cut off the water supply to upper floors.

Network infrastructure

Information technologies are fundamental to modern business operations and generally represent a small energy expenditure compared to equipment such as water heaters and HVAC units. Lack of connectivity can severely disrupt business operations and, in hospitals, can even reduce the ability of medical staff to care for patients.

Air conditioning

Providing optional backup power for air conditioning systems can be expensive as the required generator capacity increases significantly. However, there are many cases where the loss of air conditioning can be very disruptive to business operations and the additional cost may be justifiable from a business perspective. For example, the loss of air conditioning can drive away potential customers in restaurants and retail stores.

Conteúdo Relacionado

There should be no impulse purchases when it comes...
Air balancing is a fundamental design skill for HVAC...
Beam construction is a broad field that covers a...
One of the first things you need to decide...
This article explains the types of retaining walls and...
The retaining wall is an important structure that provides...
Water bills are not the only operating cost associated...
This article explains the construction of a single angle...
Most of the energy consumed by buildings is in...
Movement joints are widely used in structures because they...
In January, New York energy company Consolidated Edison Inc...
Expansion joints in concrete are particularly important in the...
Consolidation liquidation is a different type of liquidation we...
There are cases where some areas of the building...
Air ducts are often hidden in residential and commercial...
The difference between unidirectional cards and bidirectional cards must...
There is a common misconception that renewables are expensive...
Borehole surveys and borehole layout planning are carried out...
Do you worry about going to the bathroom and...
Back to blog

Leave a comment

Please note, comments need to be approved before they are published.